Skip to the page
Fire Door Repair Co.Get a quote
Site menu

How big can the gap around a fire door be?

16 Nov 2026 · about 2 minutes

Government guidance treats gaps over 4mm at the sides and top as a fault. The bottom gap is set by the door's own test evidence and is usually larger. Gaps that are too wide let smoke and fire through before the seals react.

Gaps are the most common fault on fire door checks. They are also the easiest to measure, which is why surveyors and fire risk assessors look at them first.

The 4mm guide

The government fire door guidance treats a gap of more than 4mm between the door and the frame as a fault, other than at the bottom. In practice most fire door certificates set the gap at the sides and head at around 2 to 4mm. Too tight is a problem too: a door that binds may not close on its own.

The bottom gap

The gap under the door is set by the door’s test evidence, not by the 4mm figure. It is usually larger, because floors are uneven and the door has to clear carpets or thresholds. Where the door needs to hold back cold smoke, a drop seal or threshold seal may be needed to close the bottom gap. Check the manufacturer’s data or the certificate for the right figure for your doors.

How gaps are measured

A gap gauge or a set of feeler gauges is pushed into the gap at several points down each side and along the head, with the door closed. One reading is not enough: a door can be 3mm at the top and 6mm at the bottom of the same edge if it has dropped.

Why gaps open up

  • Hinges wearing or screws loosening, so the leaf drops on the latch side.
  • Timber shrinking in heated buildings.
  • Frames moving after building work.
  • Doors trimmed to clear new flooring without regard to the certificate.

How they are fixed

Small gaps are often closed by tightening or packing the hinges, or adjusting the keep. Larger gaps need a hardwood lipping glued and pinned to the edge of the leaf, then planed to fit. Very large or uneven gaps can mean the frame has moved or the leaf is beyond repair. BS 8214 covers how repairs to timber fire doors should be made.

Gaps are a standard part of fire door maintenance and of a remedial programme. For a block or school with many doors to fix, a fire door repair company can price the work from your survey.